How to Design an Off-Grid Solar System

Put the pieces together in the right order, from your daily energy to a system that works as one.

An off-grid system is only as good as its weakest match. A big battery is no use if the inverter can't draw from it. Great panels won't help if the controller can't take their voltage on a frosty morning. And a generator that's too small will stall the moment the charger and the kettle run together.

This guide puts the design steps in order and shows how each choice feeds the next. It uses two worked examples that run all the way through:

Every figure below is an example, not a design for your site or a product recommendation. Your loads, your location and the gear you choose will change the numbers.

1. Who this guide is for

If you're on the grid and want backup for blackouts, see Solar Battery Backup: What Can You Run During a Blackout?.

2. The design order, and why it matters

Step You decide It feeds
1 Daily energy and peak load Everything
2 System voltage Every component
3 Inverter Battery current, backup
4 Battery Panels, chargers
5 Panels Controller
6 Charge controller Compatibility
7 Backup charging Compatibility
8 Compatibility check Installer
9 Qualified installation The working system

The order matters because each step uses the answer from the one before. The most common design mistake is to start with a product: "I've got a deal on a battery", or "this all-in-one kit looks good". Then you work backwards and find it doesn't fit your loads. Start with your loads and let them choose the gear.

The nine-step design order for an off-grid system: daily energy and peak load, system voltage, inverter, battery, panels, charge controller, backup charging, compatibility check, and qualified installation by a licensed electrician for all 240V AC work.
Planning is something you can do yourself. The installation needs qualified people.

Step 1: Daily energy and peak load

What you decide: how many watt-hours you use in a day, and the most watts that could run at the same moment.

  1. List everything you'll run, with its watts and its hours on a normal day.
  2. Multiply watts × hours for each item, and add them up.
  3. Add about 20% for losses in the inverter, battery and wiring.
  4. Separately, add up the watts of everything that could run at the same time. That's your peak load.
  5. Note your hardest-starting motor. Motors often draw two to three times their running watts for a moment when they start.

See How to Calculate Your Home or Workshop Power Needs, or use the Daily Power Needs Calculator.

The workshop The shed
Loads LED lights, bar fridge, laptop, drop saw, tool chargers, radio LED lights 30W × 4h, radio 10W × 5h, tool battery charger 100W × 1h, laptop 50W × 1.3h
Daily energy before margin About 1,870Wh 335Wh
With 20% margin About 2,250Wh 402Wh, about 400Wh
Peak load Saw, lights, fridge and radio: 1,950W Charger, lights, radio and laptop: 190W
Hardest motor Drop saw None

Common mistakes at this step:

Step 2: System voltage

What you decide: 12V, 24V or 48V.

For the same power, a higher voltage means less current, which means thinner cable and less energy lost as heat. Start from your peak load:

Peak load through the inverter Usual choice
Up to about 1,500W 12V
About 1,500 to 3,000W 24V
Over about 3,000W, or a system that will grow 48V

See 12V, 24V or 48V? Picking Your System Voltage, or use the 12V / 24V / 48V Picker.

Battery, inverter, controller and any charger must all be built for the system voltage. Changing it later usually means replacing most of them. If you think you'll grow, choose for the bigger system now.

Step 3: Inverter

What you decide: the inverter's continuous and surge ratings, the waveform, and whether it needs to be an inverter-charger.

Use the Inverter Size Calculator, and see Running Power Tools Off Solar for motor surges.

Battery current: the number that links Step 3 to Step 4

Battery current ≈ AC watts ÷ inverter efficiency ÷ system voltage

Inverter fully loaded at 3,000W (90% efficiency, example) Battery current
12V ≈ 278A
24V ≈ 139A
48V ≈ 69A

This table is why big inverters belong on 24V or 48V.

Idle draw: the hidden load

An inverter uses power just being switched on. Check the no-load or idle figure on the data sheet. For example, a 20W idle draw (example figure, the same as in the battery bank guide) left on for 24 hours uses 20 × 24 = 480Wh a day. That's about a fifth of the workshop's daily energy, before a single tool is switched on. Add the idle draw to Step 1, and use a power-saving or search mode, or switch the inverter off, when you can.

Common mistakes at this step:

Step 4: Battery

What you decide: how much energy to store, which battery, and whether it can deliver and accept the currents involved.

Rated energy needed = daily energy × days without sun ÷ usable fraction

The usable fraction (depth of discharge) comes from the battery's data sheet. Lithium iron phosphate (LiFePO4) batteries commonly allow most of their rated energy to be used. Take the real figure from the sheet.

The workshop The shed
Daily energy 2,250Wh 400Wh
Days without sun 2 2
Usable fraction (example) 0.8 0.8
Rated energy needed 2,250 × 2 ÷ 0.8 = 5,625Wh 400 × 2 ÷ 0.8 = 1,000Wh
Example choice Three 2,560Wh modules (25.6V 100Ah, example), 7,680Wh One 12.8V 100Ah battery (example), 1,280Wh

Then check the battery against the rest of the system. The current checks come straight from its data sheet:

See How to Size a Battery Bank for an Off-Grid System and LiFePO4 Batteries Explained.

Common mistakes at this step:

Step 5: Panels

What you decide: how many watts of panels you need, and whether they can refill the battery after a cloudy run.

Minimum array (W) = daily energy ÷ winter peak sun hours × (1 + loss allowance)

Use winter peak sun hours for your location from a reliable solar data source. The examples use 3 hours and a 30% loss allowance, both example figures.

The workshop The shed
Minimum array 2,250 ÷ 3 × 1.3 = 975W 400 ÷ 3 × 1.3 ≈ 173W
Smallest sensible choice Three 400W panels, 1,200W One 200W panel

The refill check: the step most people miss

An array that just covers a winter day keeps up on sunny days, but it can't refill a battery you've drained over a few cloudy days. Only the energy left over after the day's use goes back into the battery.

Example Array Winter output Surplus Energy to put back (2 days) Days to refill
Workshop 1,200W ≈ 2,770Wh ≈ 520Wh 4,500Wh ≈ 8.7 days
Workshop 1,600W ≈ 3,690Wh ≈ 1,440Wh 4,500Wh ≈ 3.1 days
Shed 200W ≈ 460Wh ≈ 60Wh 800Wh ≈ 13 days
Shed 400W ≈ 920Wh ≈ 520Wh 800Wh ≈ 1.5 days

In both examples, one extra panel turns a recovery of a week or more into a few days. Panels are usually the cheapest part of the system to add. Alternatively, keep the smaller array and plan on a generator (Step 7) for recovery.

See What Size Solar System Do I Need? and the Solar Array Size Calculator.

Common mistakes at this step:

Step 6: Charge controller

What you decide: a controller (usually MPPT for anything but the smallest systems) that suits both the current to the battery and the panels' voltage.

Current: array watts ÷ system voltage, plus a margin.

Voltage: panels in series add their voltages, and panel voltage rises on cold mornings. The cold-morning string voltage must stay under the controller's maximum PV input voltage. That limit is absolute: going over it can destroy the controller.

Cold-morning voltage = panel Voc × panels in series × (1 + temperature coefficient ÷ 100 × (coldest °C − 25))

Illustration: this uses the default example panel in our MPPT calculator (Voc 37V, coefficient −0.28% per °C). It isn't a real product.

Also check the controller's maximum PV short-circuit current, and that it has a charging profile for your battery chemistry. All-in-one inverter-chargers with a built-in MPPT need exactly the same checks.

Use the MPPT Controller Size Calculator with your real panel's label figures, and see PWM vs MPPT Charge Controllers.

Common mistakes at this step:

Step 7: Backup charging

What you decide: how you'll get through the worst weeks. The options are a generator, extra panels, a bigger battery, or cutting back.

For a generator feeding an inverter-charger:

Generator continuous rating ≥ (charge current × charging voltage ÷ charger efficiency) + loads running at the same time

The workshop:

The shed: at 400Wh a day with 400W of panels, a generator may not be needed. A small portable charger, or simply easing off on a long grey spell, may do.

Most inverter-chargers let you set an AC input current limit to stop them overloading the generator. Check the manual. See Generator Backup for an Off-Grid Solar System.

Common mistakes at this step:

Step 8: Compatibility check

This is where many DIY designs go wrong. Before you buy, check every match against a document, such as a manual, data sheet or compatibility list, not against a seller's listing:

Step 9: Qualified installation

Planning is something you can do yourself. The installation needs to be done properly:

10. The two examples, side by side

Part The workshop The shed
Daily energy 2,250Wh 400Wh
Peak load 1,950W 190W
System voltage 24V 12V
Inverter 2,500 to 3,000W pure sine inverter-charger 300 to 500W pure sine
Battery current at peak ≈ 90A ≈ 18A
Battery About 5.6kWh needed; three example modules, 7.7kWh About 1kWh needed; one example 12.8V 100Ah, 1.28kWh
Panels 1,200 to 1,600W 200 to 400W
Controller ≈ 67A before margin, at 24V ≈ 33A before margin, at 12V
Backup Generator above about 2,900W continuous Possibly none

These are planning estimates only, not a system design, wiring specification or safety assessment.

11. Design troubleshooting: when the numbers don't work

Problem in your plan Likely cause What to try
Battery current is huge (hundreds of amps) System voltage too low for the load Move up to 24V or 48V (Step 2)
Battery is enormous and expensive Too many days without sun, or high daily energy Cut loads, plan a generator, or accept fewer days
Refill takes a week or more Array only just covers a winter day Add panels, or plan generator recovery
Cold-morning voltage is over the controller limit Too many panels in series Fewer in series, more strings, or a controller with a higher input limit
Generator would be overloaded Charger and loads together exceed its continuous rating Lower the charger current or AC input limit, or use a larger generator
Inverter idle draw is a big share of daily energy Large inverter left on all day Power-saving mode, a timer, or switching it off
Battery can't charge on winter mornings Charging temperature limit A heated model, a warmer location, or delayed charging

12. Mistakes that cost the most

  1. Starting with a product instead of the loads.
  2. Choosing 12V for a big inverter.
  3. Sizing the panels for summer.
  4. Skipping the refill check.
  5. Checking the controller's amps but not its voltage.
  6. Forgetting inverter idle draw.
  7. Buying parts that don't talk to each other, such as battery communication and charging profiles.
  8. DIY wiring that needs a licence.

13. Frequently asked questions

Can I design my own off-grid system?
You can plan it, and this guide and the worksheet are made for that. The installation, including anything on 240V AC wiring or panel strings over 120V DC, must be done by licensed and qualified people.

Should I buy an all-in-one inverter-charger?
It makes a neat install. Check its built-in solar controller limits (voltage, current and power) exactly as you would a separate controller, and check that the battery is on its compatibility list.

How many days without sun should I plan for?
It's a trade-off between cost and convenience. Two days is a common starting point for a workshop. More days mean a bigger battery and more panels to refill it, or a generator.

Is 48V always better?
Not for a small shed. 48V suits bigger systems. A 200W shed is simpler and cheaper at 12V.

Can I add more batteries later?
Only within the maker's rules. Many require the same model, and some don't allow new modules to be added to an old bank. Plan for growth now if you can.

Do I need a generator?
Not always. Extra panels often solve winter recovery more cheaply. A generator makes sense for long grey spells, heavy winter loads or a system that must never go flat.

14. Quick summary

Safety: in Australia, any work on 240V AC wiring, including connecting an inverter, battery or solar system to a home's switchboard or fixed wiring, must be done by a licensed electrician. Grid-connected systems also need approval from your electricity network.

Handy gear

These are examples to compare, not a recommendation for your home. Check any model's data sheet against this guide.

Plug-in power meter

Plug-in power meter

Measures your loads for the load list step.

Check Price on Amazon

As an Amazon Associate I earn from qualifying purchases. Prices and availability are shown on Amazon.

← Back to all guides

Related guides

↑